46-648 Jupiter Magnetostrictive Transmitters
13
1.6.4.2 Measurement Type: Interface Only
Display Action Comment
1
Status
IfcLvl
% Output
Loop
Transmitter Display Transmitter default display. Status, Interface Level, % Output, and
Loop values cycle every 8 seconds.
2
IfcLevel
xxx.xx
Transmitter Display Interface level measurement in centimeters or inches
3
% Output
xx.xx%
Transmitter Display Interface level as a percentage of loop current span
4
Loop
xx.xx mA
Transmitter Display Loop current output (mA)
5
MeasType
Select type of measurement Choose Ifc Only
6
Units
Select units of length Choose cm or in
7
Probe Ln
xxx.x
Enter exact length of probe 6–420 inches (15.24–1066.8 cm)
8
Set 4mA
xxx.xxlu
Enter the PV value for 4 mA
point
Enter 4 mA point in level units
9
Set 20mA
xxx.xxlu
Enter the PV value for 20 mA
point
Enter 20 mA point in level units
10
Lvl Ofst
xxx.xxlu
Enter the level offset value Changes zero level as referenced from probe tip
11
Damping
xx.x s
Enter damping filter time 0–1 second in 0.1 increments
1–25 seconds in 1.0 increments
12
Fault
22mA
Select loop current under
fault condition
3.6 mA, 22 mA or Hold
13
Poll Adr
xx
Enter HART polling address
number
0–15
14
Trim 4
xxxx
Adjust 4 mA point Attach a meter to the output. If the output does not equal 4 mA,
adjust the value of the display until the meter reads 4 mA
15
Trim 20
xxxx
Adjust 20 mA point Attach a meter to the output. If the output does not equal 20 mA,
adjust the value of the display until the meter reads 20 mA
16
Loop Tst
Enter a mA value Set mA output to a value between 3.6 and 22.0 mA
17
DeadBand
xx.x
Factory Setting Diagnostic, factory setting
18
Snsr Mnt
Enter mounting type MLI Top (external probe; transmitter top mounted)
MLI Bot (external probe; transmitter bottom mounted)
Dir Near (NPT, BSP, and 600# or less flanged probe)
Dir Ext (flanged probes 900# class and over)
19
Trim Ifc
xx.xx
Enter value to adjust Interface
reading
-20.00 inches Lvl Trim 20.00 inches
20
F1 Cnts
Display only For factory diagnostic use
21
New Pass
Xxx
Enter new password Use up and down keys to select desired value (0–255)
22
Language
(select)
Select from English or
Spanish
Changes display language
23
Jupiter HT
Ver 3.0A
Display only Product software version