46-648 Jupiter Magnetostrictive Transmitters
17
1.6.4.4 Measurement Type: Level & Interface
Display Action Comment
1
Status
Level
% Output
Loop
Transmitter Display Transmitter default display. Status, Level, % Output, and Loop
values cycle every 8 seconds.
2
Level
xxx.xx
Transmitter Display Level measurement in centimeters or inches
3
% Output
xx.xx%
Transmitter Display Level as a percentage of loop current span
4
Loop
xx.xx mA
Transmitter Display Loop current output (mA)
5
IfcLevel
Transmitter Display Displays interface level
6
MeasType
Select type of measurement Choose Lvl&Ifc
7
Units
Select units of length Choose cm or in
8
Probe Ln
xxx.x
Enter exact length of probe 6–420 inches (15.24–1066.8 cm)
9
Set 4mA
xxx.xxlu
Enter the PV value for 4 mA
point
Enter 4 mA point in level units
10
Set 20mA
xxx.xxlu
Enter the PV value for 20 mA
point
Enter 20 mA point in level units
11
Lvl Ofst
xxx.xxlu
Enter the level offset value Changes zero level as referenced from probe tip
12
Damping
xx.x s
Enter damping filter time 0–1 second in 0.1 increments
1–25 seconds in 1.0 increments
13
Fault
22mA
Select loop current under
fault condition
3.6 mA, 22 mA or Hold
14
Poll Adr
xx
Enter HART polling address
number
0–15
15
Trim 4
xxxx
Adjust 4 mA point Attach a meter to the output. If the output does not equal 4 mA,
adjust the value of the display until the meter reads 4 mA
16
Trim 20
xxxx
Adjust 20 mA point Attach a meter to the output. If the output does not equal 20 mA,
adjust the value of the display until the meter reads 20 mA
17
Loop Tst
Enter a mA value Set mA output to a value between 3.6 and 22.0 mA
18
DeadBand
xx.x
Factory Setting Diagnostic, factory setting
19
Snsr Mnt
Enter mounting type MLI Top (external probe; transmitter top mounted)
MLI Bot (external probe; transmitter bottom mounted)
Dir Near (NPT, BSP, and 600# or less flanged probe)
Dir Ext (flanged probes 900# class and over)
20
Trim Lvl
xx.xx
Enter value to adjust Level
reading
-20.00 inches Trim Lvl 20.00 inches
21
Trim Ifc
xx.xx
Enter value to adjust Interface
reading
-20.00 inches Trim Ifc 20.00 inches
22
F1 Cnts
Display only For factory diagnostic use
23
F2 Cnts
Display only For factory diagnostic use